Compact Bulkhead & Exit Sign
The nD8611 is a compact LED bulkhead is designed for use in heavy industrial environments including process plants, refineries and bonded warehouses.
Compact and lightweight, this Zone 2 exit sign is ideal for building, walkway and stairwell escape route signage. The die-cast Aluminium bulkhead with integral battery backup provides instant 100% light output in emergency mode. It can run in maintained or non-maintained modes and features automatic battery monitoring and fault indication.
Available with self-adhesive running man decals, the nD8611 is compliant with ISO 7010 and ASR A1.3 (Viewing distance = 22m).
- 
          
          Compact and lighweight LED bulkhead with integral battery
 - 
          
          Available with running man exit decal to ISO 7010
 - 
          
          Also available for use with central battery systems
 
  nD811 without running man decal
  ND 8611 Dimensions
Luminaire Ratings
| Product Reference | Integral Battery | Colour Temperature (K) | Lumen Output (lm) | Power (W) | Ambient Range | Weight (KG) | 
|---|---|---|---|---|---|---|
| LX2ND8611201 | No | 6500 | 100 | 4W | -20°C to +40°C | 0.9 | 
| LX2ND86112013 | Yes | 6500 | 100 | 4W | -20°C to +40°C | 1.3 | 
Note - Lumen output in Emergency mode is unchanged. Running man decal available to be ordered as an accessory.
Options
| ZB | Preparation for use with a central battery system | 
|---|---|
| RR | Looping facility (2 x M20 entries same side) | 
| ECG | 24V extra-low voltage | 
| 60 | 60-minute emergency duration (100% output) |